i have had a recessed ceiling light over a shower in my home for twenty
years. i have always have had the light go out periodically for maybe
5 to 10 minutes. recently i remodeled the shower area and changed out
the entire light unit with an "IC" rated can light. trouble is the
light still goes out periodically for maybe 5 to 10 minutes. can
anybody recommend a remedy?

  #2   Report Post  
Posted to alt.home.repair
John Grabowski
 
Posts: n/a
Default recessed ceiling light troubles


"ww" wrote in message
oups.com...
i have had a recessed ceiling light over a shower in my home for twenty
years. i have always have had the light go out periodically for maybe
5 to 10 minutes. recently i remodeled the shower area and changed out
the entire light unit with an "IC" rated can light. trouble is the
light still goes out periodically for maybe 5 to 10 minutes. can
anybody recommend a remedy?


What type and wattage of bulb are you using? Usually an IC fixture is only
rated for 75 watts. It sounds as though it is going off on thermal
protection.

  #3   Report Post  
Posted to alt.home.repair
Scott Townsend
 
Posts: n/a
Default recessed ceiling light troubles

Yeah that was what I was thinking. That black gizmo at the top of the can
detects the heat and cuts the power.

The can lights are not really rated for high wattage bulbs, and you also
have to look at the Baffle you use too. If its an enclosed baffle with a
Lens, it might lower the wattage you can use as the hear will build up
faster.

Scott-
"John Grabowski" wrote in message
...

"ww" wrote in message
oups.com...
i have had a recessed ceiling light over a shower in my home for twenty
years. i have always have had the light go out periodically for maybe
5 to 10 minutes. recently i remodeled the shower area and changed out
the entire light unit with an "IC" rated can light. trouble is the
light still goes out periodically for maybe 5 to 10 minutes. can
anybody recommend a remedy?


What type and wattage of bulb are you using? Usually an IC fixture is
only
rated for 75 watts. It sounds as though it is going off on thermal
protection.



  #4   Report Post  
Posted to alt.home.repair
 
Posts: n/a
Default recessed ceiling light troubles

John Grabowski wrote:
"ww" wrote in message
i have had a recessed ceiling light over a shower in my home for twenty
years. i have always have had the light go out periodically for maybe
5 to 10 minutes. recently i remodeled the shower area and changed out
the entire light unit with an "IC" rated can light. trouble is the
light still goes out periodically for maybe 5 to 10 minutes. can
anybody recommend a remedy?


What type and wattage of bulb are you using? Usually an IC fixture is only
rated for 75 watts. It sounds as though it is going off on thermal
protection.


Lots of recessed lights have thermostats these days, but 20 years ago?
Sounds more like a broken wire or loose connection somewhere.

Nick

  #5   Report Post  
Posted to alt.home.repair
JGolan
 
Posts: n/a
Default recessed ceiling light troubles

In addition to the other two replies, which I agree with, your thermal
sensor is most likely the cause. If when you installed the can you
packed insulation material around it you may want to take the can down
and remove some to allow it to better disburse the heat, the more
breathing room the better.



  #6   Report Post  
Posted to alt.home.repair
Terry
 
Posts: n/a
Default recessed ceiling light troubles


wrote in message
...
John Grabowski wrote:
"ww" wrote in message
i have had a recessed ceiling light over a shower in my home for twenty
years. i have always have had the light go out periodically for maybe
5 to 10 minutes. recently i remodeled the shower area and changed out
the entire light unit with an "IC" rated can light. trouble is the
light still goes out periodically for maybe 5 to 10 minutes. can
anybody recommend a remedy?


What type and wattage of bulb are you using? Usually an IC fixture is
only
rated for 75 watts. It sounds as though it is going off on thermal
protection.


Lots of recessed lights have thermostats these days, but 20 years ago?
Sounds more like a broken wire or loose connection somewhere.

Nick

We installed a light in the overhead of our fibreglass bath tub shower unit.
It was designed for 115v AC and carries a warning to only use a bulb of a
certain wattage (60 watt I think?). Although it has a ceramic bulb socket;
we being conservative would therefore, if it were connected to 115 volts,
use 40 watt maximum.
IIRC it has a small black "thermal cut out" which is wired in series with
the black (hot lead). The recessed type fixture (pot light?) came with a
warning to ventilate around it; i.e. not surround it with insulation, to
avoid heat build up. Since our is in free space above the tube enclosure,
not mounted in the ceiling itself, it is well ventilated anyway.
I recall the wiring up was somewhat fiddly, due to the extra two connections
on top of the fixture before inserting and mounting it up into the mounting
hole.
There is other wise more than sufficient light in our bathroom, but no
windows. So we used our over-bath light as an emergency light; using a 24
volt, 25 watt RV type bulb powered from the two x 12 volt ex-truck
batteries in our basement that power our computers during extremely rare
power hits/failures.
BTW. We also keep a candle/holder and matches in the vanity. Amazing how
much light one candle can give with the candle holder standing in the sink,
the mirror behind reflecting the lit candle out through the open bathroom
door into the bedroom passageway. Candle can burn down safely for an hour or
two.
Meanwhile one can enjoy listening on a battery operated radio to find out
storm conditions, what caused the power outage etc. and to short wave
without all the disgusting RFI (Radio Frequency Interference) that today's
electrical gadgets produce.


  #7   Report Post  
Posted to alt.home.repair
Sev
 
Posts: n/a
Default recessed ceiling light troubles

Quick fix- maybe try 15w CF bulb?

  #8   Report Post  
Posted to alt.home.repair
RickR
 
Posts: n/a
Default recessed ceiling light troubles

Yes 20 years ago. I was selling them at the time. 40 years no, but they
came in durring the 70's if memory hasn't cut out.

Most lensed recessed are limited to 40 watts, a few at 60 and only very
rarely more.

RickR

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Funny:How many forum members does it takes to change a light bulb? Paul UK diy 3 December 21st 05 11:05 AM
Red Wire in Ceiling Light Outlet Unknown Home Repair 11 March 28th 05 08:19 PM
Recessed Light repair Camilo Home Repair 4 December 31st 04 06:32 AM
Help with adding wireless switch to ceiling light Daren Desjardins Home Repair 3 September 13th 04 07:16 PM
Strange electrical problem, outdoor motion light and indoor ceiling fan switch TCS Home Repair 2 May 17th 04 11:57 AM


All times are GMT +1. The time now is 01:53 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"