Brian December 27th 05 03:25 PM

Forced hot water - baseboard heat problem.
 

I have a small problem I need help with. I have forced hot water with baseboard heat. My expansion
tank sprung a leak last week. I replaced it by spinning the old one off and spinning the new one
on. In the process I lost some water. My problem is that now when the heat comes on I hear water
running through the baseboards. I know there's a way to bleed the zones but I have forgoten how. I
also remember it has something to do with the faucet and shut off valves at the end of each zones
run back to the furnace. One last thing, on the top of the manifold that the expansion tank
attaches to, there's a small round part with what looks like a tire valve stem on the top of it. It
has a cap on the stem and when I loosen the cap, water starts dripping out. Is this some kind of
bleeder ??? Do I leave the cap loose and let it drip ????

Thanks
Brian

Bob December 27th 05 03:51 PM

Forced hot water - baseboard heat problem.
 
The easy way, is to turn the electric off, relieve the system pressure,
replace that "small round part with what looks like a tire valve stem on the
top of it" (automatic air vent), add water to the system, turn the electric
on, and wait a few days. The cap is just there to close it off if it starts
leaking. It should normally be loose. Most times, the air will eventually
work it's way around and come out that vent.



The harder, but quicker and more positive way of getting the air out, is to
first turn off the electric, then close all (return line) shut off valves
that are between the "faucet" (boiler drain valve) and the heater. Then put
a hose on one of the drains, purge the air out by opening the drain valve,
repeat the process on each zone, and then open the shut off valves. With
this method, you need to maintain constant system pressure.



"Brian" wrote in message
...

I have a small problem I need help with. I have forced hot water with

baseboard heat. My expansion
tank sprung a leak last week. I replaced it by spinning the old one off

and spinning the new one
on. In the process I lost some water. My problem is that now when the

heat comes on I hear water
running through the baseboards. I know there's a way to bleed the zones

but I have forgoten how. I
also remember it has something to do with the faucet and shut off valves

at the end of each zones
run back to the furnace. One last thing, on the top of the manifold that

the expansion tank
attaches to, there's a small round part with what looks like a tire valve

stem on the top of it. It
has a cap on the stem and when I loosen the cap, water starts dripping

out. Is this some kind of
bleeder ??? Do I leave the cap loose and let it drip ????

Thanks
Brian