"Christian McArdle" wrote in message
. net...

Make sure the sockets are RCD protected. Although the circuit still won't
be
up to scratch and would still fail an inspection, this removes the main
potential danger.


But if it's RCD protected, don't you just need to meet ZsIn = 50V? (i.e.
1667ohm for 30mA)

To me, the regs are clear that it's *preferable* to design for TN systems to
disconnect on overcurrent rather than RCD, but seem to allow the use of
RCD's instead. (413-02-04 (ii) and 413-02-16).

What am I overlooking?

Will