"Doug Miller" wrote in message
.. .
In article , "rider89"
wrote:
wanting to feed a branch box with a 60a breaker (#6 copper) thru EMT.

This may be a stupid question, but is there anything in the NEC to
prohibit
using double #10's to get the amperage?


Yes, there is. Section 310-4 explicitly *permits* parallelling conductors
of
size 1/0 or *larger*, and thus by implication prohibits it for smaller
conductors.

--
Regards,
Doug Miller (alphageek at milmac dot com)