View Single Post
  #4   Report Post  
TURTLE
 
Posts: n/a
Default

"hvactech2" wrote in message
...
On Sun, 10 Jul 2005 17:10:56 GMT, Art Todesco
wrote:

I have a question for you hvac guys.
Can a central AC A coil ice up from
reduced air flow in the condenser
(40-50% of the condenser matted up)? I
know this can happen from low airflow in
the evaporator. And I know it can
happen when the freon is low. If yes,
can you explain what happens to
pressures when it happens? Thanks,


A partially plugged condenser will not cause a freeze up


This is Turtle.

The third NO in a row !

TURTLE