"Lurch" wrote in message
...
On 21 May 2004 08:09:02 -0700, in uk.d-i-y (Paul)
strung together this:

1. I'm going to use a spare 20Amp 'B' type MCB on the non-RCD
protected side of the CU using 4mm T+E cable. Can I use normal T+E
cable for the first 8m (up to the outside of the house) and then
connect it using a junction box, to 8m of SWA 4mm cable to the shed?

Yep, all looking good so far.


No. It must be RCD protected.

snip