In article ,
discjockey1999 wrote:
I know that the element needs to be connected via a fused spur, which
is no problem, but the towel rails i have seen have had a FCU situated
just below the towel rail. The towel rail is to be situated at the end
of the bath (Zone 1) and i'm wondering if it's safe to have an FCU
situated here or not. If not then how else could it be wired up.


Use a cord outlet to do the change from cable to heat resistant flex and
situate the FCU elsewhere - like outside the bathroom.

--