My electrican was in wiring for my new TIG welder yesterday and the
subject of conduit grounding came up. He said that the local code for
commercial spaces allows a maximum of 6' flex conduit before you have to
run a seperate groud wire inside.


Flex conduit (greenfield) and rigid are two kinda different
animals. Whereas I might consider not running a green wire
inside rigid, I would always run one inside of greenfield
or liquid-tight, given the nature of the connectors at the
ends.

Jim


--
==================================================