"Robert11" wrote in message
...
Hello:
About to buy a few Kidde P12000 Smoke alarms.
The AC wired type, with both ionization and photocell.
Looked at their on-line instructions, and was surprised
to see that they say to install on circuits that are NOT
GFCI protected.
Seems surprising.
Anyone know the reason why ?
Thanks,
Bob
-----------------
" Make certain all alarms are wired to a single, continuous (non-switched)
power
line, which is not protected by a ground fault interrupter. "
if the gfci triggers, they don't work. you may not notice the triggering for
quite some time.
|