Please can someone comment on the limitation of 3x 1.5 cables per box and
suggest a solution?
It means 3 x 1.5 cables per terminal. You will have 4 terinals in a
20A 4 terminal box.
3 lives in the 'loop'
3 neutrals.
2 in the switched live.
And finally, 4 x 1mm earths.
There you go, problem averted.
--