Mark wrote:
Hi I don't mean ON a mains circuit i mean on its own but LIKE a ring
circuit
I appreciate you mean "like a ring", however the answer is still no.
A single run of 1mm sq csa T&E is good for 12A even if burried in
insulation in a wall. So it will already cope with double the typical
MCB size you will use for a lighting circuit.
Your 600W of lighting still leaves another 800W of headroom on a
standard 6A MCB, or enough capacity for another 8 standard light fittings.
--
Cheers,
John.
/================================================== ===============\