"gary moore" wrote in message
... Im installing an
electric shower but i want to know if there is a problem if
i use plastic pipe to feed the cold water into it.I was thinking there

might
be a prob with earthing(cross bonding)


Nope, plastic's fine.

The shower itself will be earthed: it certainly doesn't rely on its water
supply pipe for this in any way.

As for any installation the incoming cold water supply should be x-bonded to
the electrical supply earth (by the meter) and to the gas.

(Q for the panel: if the incoming water pipe is MDPE and the installation
pipework is also plastic does one x-bond the stopcock?)

--
John Stumbles
-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+
-+