You are deluded.

Your method will only result in flushing the shortest part from the fill
point to the kitchen radiator. You need to:
* turn off and drain all radiators
* remove each one in turn and take it outside and wash it out with a hose
* with the radiator out, and the filling loop connected, open each

radiator
valve (with a bucket handy) and run until the water is clear

That way, you'll flush *all* the pipes *and* the radiators.
--
Cheers,
Set Square
______
Please reply to newsgroup. Reply address is Black Hole!

===============================


Thanks for putting me strait.

Ouch!! that sounds like a heavy duty job, maybe I could
just add inhibitor seeing as the system is only 2yrs old and
halt any further corrosion.

Or am I double deluded

Pete.