(grimmy) wrote on 31 Jul 2003 12:23:19 -0700:
Does anybody
know what the required angle of elevation is for the waste pipe of a
flush toilet?
The above-ground branch needs to have a fall between 18mm and 90mm per
metre run. The below ground drain needs to be no shallower than 1:40.
--
Hugo Nebula