"FrancisJK" wrote in message
...

Has anyone any opinions (silly me, of course you have) about alpha pumps?


With an alpha, as TRVs close the flow falls but the head does not rise
as in normal pumps. With a normal pump you need a bypass. So normal
pump+bypass gives constant-ish flow rate and return temperature rises
as TRVs close. Alpha gives reducing flow and a lower return
temperature.

Hence Alpha's are a good idea if you have a condensing boiler since
those are more efficient with lower return temperature. But normal +
bypass is probably better for a standard boiler since they do NOT want
a lower return temperature due to the risk of condensing causing
boiler corrosion.


--

Malcolm