Yesterday I noticed that the water pressure in my combi-boiler was below 1,
so I let in some more water upto about 2.5. However, when I turned the
central heating on it went up to over 3 and it has stayed there. Can anyone
tell me, is this dangerous? Can I use the heating? Should I reduce it a
little by bleeding a radiator?
See FAQ on Selaed CH below.
The pressure releif valve must be just on the point of opening.
Bleeding all radiators migth bring it down and letting some out a drain
point certainly will.
Look for about 1.5 bar max.
--