Heat loss calculations.
On 04/03/2021 23:05, Osprey wrote:
I am going to have to change out my boiler.
I had my whole house heating design done by underfloor heating company.
They sized boiler at 28kW ... (so currently have 30kW boiler)
Think it prudent to check sizing before I order replacement.
I know there are a plethora of €˜rad sizing programs, anybody able to recommend a good one (Stelrad, Castrads etc)
That would be pretty basic approach ... anybody aware of something that looks at whole house.
There are two things to decide first
1/. how much power you need to keep the house warm at the coldest
outside temp and wind you are likely to encounter
2/. How fast you need the place to warm up.
I sized my boiler at 1/. and forgot 2/.
This winter it was on 20 hours out of 24...
Basically an oversized boiler won't hurt - but an undersized one will
struggle
Fit the biggest that will physically fit
--