On 30/10/2020 17:44, Harry Bloomfield wrote:
Andrew pretended :
Are they fitting a magnetic filter to keep crud out of the new
boiler ?. They should and might be relying on this to collect the
rust particles.


Noiler manufacturers seem to insist on one, for the warranty. They do
only collect the rust particles - no use at all for collecting other
debris,


Some have a cyclonic filtration action as well for non magnetic stuff -
however their ability to "hang onto" the non magnetic crud is presumably
more limited.

which can still obstruct a modern boilers water passages. So
basically - if it needs flushing, it needs to be flushed before a new
boiler is fitted.


+1 or at least, it can be fitted, but isolated at its service valves.


--
Cheers,

John.

/================================================== ===============\