On 20/11/2019 07:57, Andy Bennet wrote:
As I am getting on in years and no longer fancy climbing ladders to
clean the upstairs windows, a while ago I bought one of those water fed
pole brushes and a pressurized water deionizer to do the job. I must say
that it does an absolutly brilliant job in next to no time and wished I
had invested in such a kit years ago. I use it for the downstairs
windows as well as it is so easy and fast.
But I digress...
I need to do a small amount of system pipework relocation on our
(sealed) CH system next year and the thought crossed my mind, as we live
in a very hard water area, that I could repressurize the system with
deionised water and inhibitor.
This would help to prevent scaling up and kettling noises in the boiler.
Now I know that pure water can be quite agressive in terms of corrosion
etc etc but is this a good idea or should I just forget it and top up as
normal?


I would say that since you are talking about a recirculating system,
where fresh water is introduced rarely, there is no particular advantage
to using deionised water. Many boiler makers also caution against using
softened water in the primary CH circuits.

You can get additives to suppress kettling if its already happening.
Sentinel do a "boiler noise reducer" product that works - although needs
replenishing each year IME.


--