On Thursday, 6 June 2019 15:42:41 UTC+1, David WE Roberts (Google) wrote:
On Thu, 06 Jun 2019 14:03:55 +0100, Andy Burns wrote:

wrote:

2.5 T&E is not rated to 32A, nor does it need to be on a 32A MCBed
ring.


But it is rated at up to 27A, so using a connector rated at only 24A
makes it the weak link, after all we don't know how far round the ring
this junction box is ...


Box of 222-412 ordered from Amazon.


Note that 222-412 connectors are derated from 32A down to 20A when used in a maintenance-free enclosure (see
http://enews.wago.com/art_resource.p..._download=1 ). Their 773-173 connectors are derated from 41A to 32A.