On Thursday, 6 June 2019 14:03:59 UTC+1, Andy Burns wrote:
tabbypurr wrote:
2.5 T&E is not rated to 32A, nor does it need to be on a 32A MCBed ring.
But it is rated at up to 27A, so using a connector rated at only 24A
makes it the weak link, after all we don't know how far round the ring
this junction box is ...
2.5 T&E is rated at 13.5 to 27A depending on install method.
NT
|