On Thu, 06 Jun 2019 14:03:55 +0100, Andy Burns wrote:

wrote:

2.5 T&E is not rated to 32A, nor does it need to be on a 32A MCBed
ring.


But it is rated at up to 27A, so using a connector rated at only 24A
makes it the weak link, after all we don't know how far round the ring
this junction box is ...


Box of 222-412 ordered from Amazon.

Thanks


Dave R

--