Transformer DC resistance value estimate needed
bitrex wrote:
Can anyone give me a ballpark on the DCR of this particular
small tube-PSU-type transformer to plug into PSU Designer II?
https://www.alliedelec.com/product/hammond-manufacturing/6k88vg/70009014/
** Assuming the tranny has a regulation factor of 10%, that equates to 6 volts copper loss on the primary under full load.
Rated load is 36 VA plus a little for Imag gives 40VA.
So the primary current with resistive load is 0.33amps rms.
Makes the primary R = 18ohms.
A similar, 240V tranny would have four times the primary R.
...... Phil
|