On 11/03/2019 14:41, Roger Hayter wrote:
For anyone who thinks wiring is too easy to be left to the
professionals. In our bathroom the fan permanent live is supplied from
the socket circuit (admittedly from a fused switch unit next to the
sccket in the cupboard under the sink) and the switched live is from the
lighting circuit. I don't suppose this is totally forbidden,
Er, yes it is!
but it
seems a bit eccentric to me, especially if one thinks the fan might be
isolated by the (two pole) FSU.
A fan with switched and permanent live ought to have a three pole isolator.
--
Cheers,
John.
/================================================== ===============\