On 26/07/2018 17:22, Scott wrote:
I have done some minor wiring, which in due course will be inspected.
I removed a socket and substituted a terminal block and blanking
plate. Should I have folded the conductor cables where they enter the
terminal block, or is this a thing of the past?
Either are acceptable so long as you can get a good firm termination.
The only time folding is really needed is with a small diameter wire
into a large terminal, where you may not otherwise be able to get the
screw to grip it.
--
Cheers,
John.
/================================================== ===============\