Thread
:
Curent electrical regulations
View Single Post
#
6
Posted to uk.d-i-y
Brian Gaff
external usenet poster
Posts: 10,998
Curent electrical regulations
Are you sure about that. I can think of many people around here renting out
houses that still have the old wiring from the 70s but have had work done
etc including smart meters.
Brian
--
----- --
This newsgroup posting comes to you directly from...
The Sofa of Brian Gaff...
Blind user, so no pictures please
Note this Signature is meaningless.!
wrote in message
...
On Thursday, 12 July 2018 11:37:07 UTC+1, The Natural Philosopher wrote:
Am I right in thinking that no matter how dysfunctional or prone to
nuisance tripping it is, a 30mA whole house RCD still meets current
regulations?
no, need a split CU at the minimum
And I would think an RCD that keeps nuisance tripping leaves the landlord
open to the claim that the property does not satisfy the contract.
And in a 16 year old property that is to be let, does it NEED to meet
current regulations anyway?
It needs an electrical inspection every 5 years, and anything that fails
to meet current standard at those times be brought within spec. So yes.
NT
Reply With Quote
Brian Gaff
View Public Profile
Find all posts by Brian Gaff