wrote:
All these fuses will say 415V and are generally 100A, although sometimes
less. This doesn't mean it's three-phase, unless there are three of them 
The 415V is just the voltage the component is rated to €” fuses operate on
Amps alone, the voltage is not relevant. A 100A fuse will blow just
beyond 100A whether it's at 12V or 1200V.
The same way appliance mains cables are rated to 300V or even 600V; it
just refers to the insulation resistance or safety factor of the cable.
Thank God. Ive been waiting three years for someone to answer. Oh, hang
on, they did three years ago.
Try this link...
http://bfy.tw/Ho7B
Tim
--
Please don't feed the trolls