On 03/04/2018 14:02, Graham. wrote:
On 03/04/18 13:16, Graham. wrote:

I only have the bare bones of this from my daughter at present.

She has new "wet" underfloor heating laid. The tiller was laying floor
tiles on the screed,, and cut through the tubing (angle grinder?).

Is this repairable, or is it a break up the floor and start again job?

it is at least dig enough space out to put a coupling in and then bury
it all again


Further information: It seems it was just above the floor, involving
some expanding foam that presumably he was tidying up.


In that case, you can use a push-fit coupler. I personally wouldn't be
happy with any joints *under* the screed 'cos it's a right pain if they
ever decide to leak.
--
Cheers,
Roger