View Single Post
  #11   Report Post  
Posted to uk.d-i-y
[email protected] tabbypurr@gmail.com is offline
external usenet poster
 
Posts: 12,364
Default Gas consumption, CH versus no CH

On Sunday, 1 April 2018 19:31:15 UTC+1, ARW wrote:
On 01/04/2018 19:23, tabbypurr wrote:
On Sunday, 1 April 2018 18:15:29 UTC+1, Steve wrote:

I had a call a few weeks ago where the customer said he'd been taking
meter readings and he was losing about £10 of electricity a day. He
thought it was something to do with his boiler as sometimes he had some
warm water coming out of the cold tap. Sounded like a sensible bloke,
even though what he was saying was a bit odd, so I went for a look.

Supply was nominally a TT (no sign of a rod) with an old Wylex
rewireable box. Clamp meter on + tail 10.5A, clamp meter on - tail
0.5A. Pulled the fuses an found the current was flowing in the ring. A
quick look around found a socket with a very hot screw - the live had
been nicked by the screw and was providing a nice 24 ohm earth path to
the incoming lead water main. An expensive way to heat the water in the
first few feet of lead pipe and lucky not to have had a fire.


can we put that on the diy wiki?


Before or after homeownershub post it with replies in 2020, 2023 and 2525?


Only 7 years? They've done better than that many a time.

New blood here is no bad thing, but for some reason the hohers are seldom capable of anything.


NT