Default Fuse calculation

On Friday, March 23, 2018 at 8:55:58 PM UTC+11, Bob Eager wrote:
On Thu, 22 Mar 2018 18:50:17 -0700, gopalansampath wrote:

On Tuesday, March 20, 2018 at 2:48:07 AM UTC+11, Graham. wrote:

Which is the best fuse to use (3A, 5A or 13A) with a 1.15kW electric
fire at a potential difference of 240v
1150/240=4.79 so theoretically a 5A fuse shoud do.
--

Graham.
%Profound_observation%


May be 5A will do, as "cold" heater element resistance would be higher
than normal heating.


Surely it's the other way round.

--
My posts are my copyright and if @diy_forums or Home Owners' Hub
wish to copy them they can pay me £1 a message.
Use the BIG mirror service in the UK: http://www.mirrorservice.org
*lightning surge protection* - a w_tom conductor


OOps! I stand corrected. Surely fuse rating shall be higher than % Amps.