On Friday, 23 March 2018 01:50:20 UTC, wrote:
On Tuesday, March 20, 2018 at 2:48:07 AM UTC+11, Graham. wrote:

Which is the best fuse to use (3A, 5A or 13A) with a 1.15kW electric fire at a potential difference of 240v

1150/240=4.79 so theoretically a 5A fuse shoud do.
--

Graham.
%Profound_observation%


May be 5A will do, as "cold" heater element resistance would be higher than normal heating.


But according to regulations in the UK on changing fuses it should be either a 3A for below 720W or a 13amp for above 720W .

https://www.rospa.com/home-safety/uk...hoosing-fuses/