In article ,
whisky-dave wrote:

Which is the best fuse to use (3A, 5A or 13A) with a 1.15kW electric
fire at a potential difference of 240v


If you're talking a plug fuse, the load is irrelevant. As it is to protect
the flex etc. In other words, a table light with a 20 watt bulb would be
fine with a 13 amp fuse if the cable was rated at 13 amps.

--