On 10/12/2017 21:58, John Rumm wrote:
On 10/12/2017 21:12, ss wrote:
Its my neighbours so trying to help.
Vokera compact 25A,sealed system I think.
Still gets hot water if turned to hot water only and rads off.
Fault is A01 ignition failure,flame not sensed, internal fault.
Do you actually hear it light the burner?
(and hear it spin up the fan, spark etc)?
The problem I have is with it being a neighbour I dont want to start
stripping it down, mine would be in bits by now :-)
The boiler calls for firing and the temp gauge rises by a few degrees
and then appears to cut out, the pump still appears to continue running
as it then starts making lots of gurgling noises, I am hazarding a guess
that the pump is pumping but as water is not flowing due to a blockage
(frozen) a safety circuit is cutting the gas off and creating an
ignition failure.
|