On 22/09/2017 15:52, wrote:

Sir what will happen if a European oven with 13A main fuse rating is
used in India where Standard power plugs are rated 16A after changing
European plug to the Indian plug


Any appliance that is sold for use in europe should be designed such
that its flex has adequate fault protection from a 16A circuit breaker -
since that is what would be expected in most euro countries. The UK is
unusual with the general use of 32A circuits for socket circuits - and
hence the need for additional fusing at the point the appliance connects
to the circuit.


--