MCB trips as soon as a water heating coil is used.
On Thursday, 9 February 2017 12:23:54 UTC, Harry Bloomfield wrote:
expressed precisely :
presently there is an C6 MCB can I replace it to 16 to resolve this problem
The sent from IP seems it might be Shertallai, Kerala, in India.
Ah. I wouldn't expect a 6A mcb to be powering a 16A capable cable, so no, doing that would be unwise. What power is this water heater?