On 18/11/2016 20:43, Tim Lamb wrote:
In message , ARW
writes
On 18/11/2016 16:17, Tim Lamb wrote:
I have a 9" angle grinder which consistently trips a 20 amp MCB......
You mean it trips a B type 20A MCB?
Yes. Fine elsewhere on re-wireables. Makita.
My workshop socket outlets are end fed so limited to 20 amps.
My previous workshop initially had a 20A MCB protected socket circuit,
and things like my 3kVA site transformer would trip that on switch on
about one time in five. Its fine on a B32 or C20 though.
--
Cheers,
John.
/================================================== ===============\