On Fri, 5 Dec 2003 09:09:20 -0000, Christian McArdle wrote:

This is what I did, except there is no need for fuses in the grid
switch. It is better to have only the fuse in the plug top. The grid
switch is fed from a dedicated 32A 6mm radial and feeds only a w/m,
d/w and t/d.


And 6mm from the gridswitch to the sockets? If you've dropped to 2.5mm
from the gridswitch to socket that section is not properly protected
by the 32A breaker...

--
Cheers