Default Separate ground wire to panel to ground outlets?

On Wednesday, October 8, 2014 9:39:45 AM UTC-4, TomR wrote:
This question was posted in another forum by someone that I know and I

thought that I would try posting it here to get some feedback on his behalf:



He wrote,



"In a house that has ungrounded, 2 prong outlets, with wiring in good

condition, is it acceptable (and allowed by current electrical code) to run

a separate ground wire from the outlets back to the ground at the panel, in

order to be able to replace the 2 prong outlets with 3 prong outlets?

Existing wiring is in very good shape."



Thanks.



*Article 250.130(C) in the National Electrical Code gives the options, but the short answer is yes.

John Grabowski