View Single Post
  #5   Report Post  
Posted to alt.home.repair
The Daring Dufas[_8_] The Daring Dufas[_8_] is offline
external usenet poster
 
Posts: 4,463
Default Seems residential home pre-sale inspections cannot be run forthe A/C side if the outside air temp is below 60F

On 1/20/2013 11:22 AM, Ernie wrote:
The Daring Dufas wrote:

The most inexpensive residential AC systems lack a factory
installed head pressure control which is why it's not prudent
to run them in cold weather.


Why couldn't a thermostat that can sense condenser coil temperature be
used to turn on the fan when the coils reach some pre-determined
temperature?


That's exactly what the fan speed modulators do in the links I provided.
The ICM manufactured controls I use, come with a temperature sensor
that's attached to the high pressure line on the condenser coil to
operate the control. ^_^

TDD