On Mar 16, 5:17*pm, "Dave Liquorice"
wrote:
On Fri, 16 Mar 2012 14:02:12 +0000, John Rumm wrote:
Two 3kW kettles probably would take out the plug fuse in under a minute..


Thats not quite a 100% overload. I think the average BSwhatever
plug top fuse would last longer than that(*). Wether the plug top
could take the heat generated is another matter...


A strictly 3kW kettle, 3000W, is 12.5A at 240V.
I think most are quoted as a range such as 2960-3180W etc.

Coopers BS1362...
- 1.6*In (20.8A) MIN of 30min - 5000W
- 1.9*In (24.7A) MAX of 30min - 6000W.