On Mar 16, 2:08*pm, whisky-dave wrote:
On Mar 16, 1:06*pm, "js.b1" wrote:
Isn;t there a problem with 10a fuses getting hot in teh plug if
someone uses that lead for a 3kw kettle.


No, a fuse dissipates 1W at rated current.

For a 10A fuse (data from Coopers)...
- 1 * In (10A) for min of 1000hrs continuous.
- 1.6 * In (16A) for min of 30min continuous.
- 1.9 * In (19A) for MAX of 30min continuous.

So even with a 10A fuse you can still pull 16A for 30min continuously.


Cheapest is education.


Are you saying we use students as cheap fuses ;-)


Some lecturers could be, only time they would ever be a bright spark...