I suspect part of the problem *IS* that people think the fuse will
always protect them if they are doing something wrong.
I am surprised at how many people think a 13A fuse blows immediately
you go above it.
Equally, many do not understand the thermal insulation effect of a
rug, cushion or curtains on an extension lead. One reason I changed
all leads to 1.5mm H07RNF and 10A fuses, the rubber purely because it
is a little more robust to objects dropped on it (and at the time
cheap whereas now I notice it has jumped in price).
No idea if a fridge/freezer inrush mandates 13A over 10A or 7A;
standard fuse sizes are 3A 5A 13A. A lot of cheap consumer products
seem to be using internal components as the fuse :-)
Cheapest is education.
Inrush of around 3x running current would give in the region of an amp
on a modern domestic appliance. Plug fuses don't seem to fussed about
motor startup current in practice, perhaps partly because these fuses
are mostly rated at well above motor rated i anyway.