Isolation transformer draws excessive current under no load condition
On Feb 18, 4:22*pm, "Phil Allison" wrote:
"Cydrome Leader"
I'd say your transformer is bad or somehow connected wrong.
** No way.
The OP's data shows it is operating normally and correctly.
10 degrees temp rise and a PF of 0.15 is A-OK.
.... *Phil
Why doesn't the transformer data sheet include idle current, power
factor, etc.? Or is it embedded in some transformer standard I have to
spend 2000 swiss francs to get?
|