On Oct 12, 7:56*am, "RBM" wrote:
"RBM" wrote in message

...







"Mikepier" wrote in message
....
Last week, I posted about running 12/2 wire for a kitchen reno. Well
all the circuits are run. I decided on running all 12/2 instead of
12/3 and splitting circuits. Looking ahead to outlets, had a question.
I think I know the answer, but just wanted to confirm.


I ran 4 new circuits for the fridge, microwave/range hood, and counter
outlets. Am I allowed to use regular 15A outlets? For the counter
outlets, I am using regular 15A Decora and GFI's, and for the fridge,
microwave just wanted to use regular outlets, like the kind you can
get a 10Pk for like $5 at Lowes.


15 amp outlets are fine. The refrigerator doesn't need to be GFCI
protected, but all the counter outlets do. A 15 amp GFCI outlet has a 20
amp feed through


Just to clarify. A single 15 amp outlet can't be installed on a 20 amp
dedicated circuit, but a duplex is fine



- Hide quoted text -

- Show quoted text -- Hide quoted text -

- Show quoted text -


This is another example of things in the code that don't seem to make
any sense, at least to me. If one can install multiple 15 amp
outlets on a 20 amp circuit, why the restriction on installing just
one?

And while we're at it, the code also says you can use a 20 amp single
outlet on a 15 amp circuit, but you can't install multiple 20's on a
15 amp circuit.

Why the big distinction between single versus multiple outlets?