Default 15A outlets on 20A circuits


"RBM" wrote in message
...

"Mikepier" wrote in message
...
Last week, I posted about running 12/2 wire for a kitchen reno. Well
all the circuits are run. I decided on running all 12/2 instead of
12/3 and splitting circuits. Looking ahead to outlets, had a question.
I think I know the answer, but just wanted to confirm.

I ran 4 new circuits for the fridge, microwave/range hood, and counter
outlets. Am I allowed to use regular 15A outlets? For the counter
outlets, I am using regular 15A Decora and GFI's, and for the fridge,
microwave just wanted to use regular outlets, like the kind you can
get a 10Pk for like $5 at Lowes.

15 amp outlets are fine. The refrigerator doesn't need to be GFCI
protected, but all the counter outlets do. A 15 amp GFCI outlet has a 20
amp feed through


Just to clarify. A single 15 amp outlet can't be installed on a 20 amp
dedicated circuit, but a duplex is fine