millinghill wrote:
Check the small diameter line to the pressure switch...perhaps it's
where the problem is.

Otherwise, sounds like classic case of the waterlogged pressure tank.

32 gal isn't real big, a small change in pressure is a good volume.

I'd drain the tank and reset the pressure and see if the symptoms
improve....I'm betting they will.


I'll check the line to the pressure switch (located on the pump).
I don't follow what draining the tank will do. Can you explain?


That's when you need to check pressure and reset it.

If there's a pinhole leak in the bladder, that'll rezero it and the
behavior will be better (for a while) until lose more air volume if it
does have a leak...

--