"JJ" wrote
About to wire up the new kitchen (yup, all under BCO and needing part
P signoff) and all the sockets are mounted and conduit in place.
I now have a choice
4mm T&E radial on 32A RCBO
or
2.5mm T&E ring on 32A RCBO
both seem equally valid according to regs and my calculations.
I can see the argument both ways, the ring is more traditional for UK
but entails longer checks and radial in simpler but entails getting
hold of some 4mm T&E (need to order it I think, nobody seems to stock
it round here).
Whats the feeling on this here?
Ta
From a DIY rather than electro-technical perspective, 2.5 will be easier to
work with.
Phil