"Dick Keats" wrote in message
...
Asking for help.
Have a General 350 table saw not currently hooked up.
Will be moving it to a barn/workshop.
Motor specs a 3 HP, 220 V, 1 Ph., 11.7 A
Will 10/3 w/ground and a 30 A 220 breaker satisfy the load requirement?
Thanks for any help.
Dick in Texas


Yes, but its overkill. You only need two conductors and ground, and 20 amp
double pole breaker is more than sufficient