Thread: furnace problem
View Single Post
  #5   Report Post  
Posted to alt.home.repair
Tony Hwang Tony Hwang is offline
external usenet poster
 
Posts: 6,586
Default furnace problem

wrote:
I keep my thermostat set at 64 degrees. When I woke up this morning,
the house was 59 degrees inside. I left for a little bit and came back
to see the house was now 58 degrees inside. I bumped the t-stat up to
70. About 15 minutes later, the furnace clicked on and got the house
up to 62 degrees before shutting off again. It is now 60 degrees in
the house and the furnace has not came back on. It has been about 30
minutes since it shut off. What could be the problem?

Thanks

Hi,
What kind 'stat? old analog type or digital? Does it have batteries?
If you jump R and W terminal furnace should come on to heat.
If it is old mercury bulb type stat maybe it has tarnished contacts or
loose connection causing to behave like that. Time for a programmable
digital one. Easy to swap out.