dennis@home wrote:


"Peter Hemmings" wrote in message
. uk...


The reason I was not going to shut all valves was that I have 2 towel
rads which are never shut/adjusted so I thought I would never get to
the state when everything was shut!


If that is the case you don't need a bypass.

Mine frequently has all the valves closed as it is controlled by 5 two
port valves that shut whenever nothing wants heat, a bypass is essential
then.


Oooops .....

Mine is the same, I have 2 2-port valves (and the two towel rads are on
one of the loops controlled by a valve), so I DO need the bypass.



Regards